Semiconductor Fab Cuts Unplanned Maintenance by 95%+, Saves $85,700 Annually with Process Vacuum (PVAC) Treatment Program

Total Value Delivered: $85,700
Story Image

Background

One U.S.-based semiconductor fab faced long-term challenges in the operation and maintenance of their liquid-ring process vacuum (PVAC) system, primarily in the form of microbial fouling. Specifically, the fab's biofilm contained high levels of iron, a corrosion byproduct.

This fouling impacted heat transfer efficiency and system performance, and required frequent, unplanned maintenance of the heat exchangers for cleaning. Maintenance frequency ranged from semi-annually to quarterly or, in some cases, monthly. The customer brought the issue to the attention of their Nalco Water team.

Root-Cause Analysis

Working on-site with the customer, the Nalco Water team found substantial levels of slime-forming bacteria in the heat exchangers, caused by mineral oil within the units, which was added at the point of manufacture for in-transit corrosion protection.

Due to the fab's production demands, new PVAC units were started up quickly, with no time to remove the oil or clean internal surfaces. Once an oil-contaminated unit was up and running, the compression step of each operating stage moved the oil throughout the unit. This embedded the oil into the surfaces of the cast iron housing. The oil would settle throughout the unit and cause bacteria to grow, as a water/oil interface is an excellent starting point for bacterial growth.

Another contributing factor was the lack of rotation among the PVAC units. Facilities often have more than one PVAC unit and may only require one unit to run at any given time. This period of downtime can accelerate bacterial build-up in the exchanger due to the absence of flow; microbio growth favors stagnant water environments.

Lastly, the team confirmed a comprehensive understanding of the systems' metallurgy. Although the biofilm contained high amounts of iron, any chemical corrosion protection program must ensure all wetted metals were protected. Iron levels in the system were sometimes as high as 30 ppm, with water in the system periodically turning red as a result.

Solution

Nalco Water often uses an integrated mechanical/operational/chemical approach in its solution-development process. Here are the specific steps implemented to resolve these problems and prevent future occurrences.

Mechanical / Operational

  • Cleaning of new PVAC units prior to being put online, to remove all traces of mineral oil
  • Customer staff received a four-hour training on proper maintenance of the PVAC units
  • Maximum PVAC unit run time was set to one week, to support proper equipment rotation
  • Operating performance of all PVAC units was monitored via Service Intelligence, powered by ECOLAB3D™. System data helped fab personnel identify when units were performing out of spec, requiring additional corrective action.

Chemical: Microbio Control

Resolving the microbial fouling was the team's first priority. Nalco Water's Selecticide™ test enabled the team to choose a biocide with the highest potential effectiveness and minimal operational risk. The test compares the performance of various biocides across samples of system water in a particular application and assesses the microorganism count reduction in each sample. As a result, the test helps eliminate guesswork by indicating the appropriate biocide and optimum dosage range for a particular system.

Chemical: Corrosion Control

A corrosion-control chemistry was added to the program for the purpose of minimizing iron corrosion.

Results

Exchangers were examined after each change in the program. Over a two-year period, heat exchangers were pulled eight times, each time showing progressively less biofilm.

Before the Nalco Water solution, cleaning frequency ranged from monthly to quarterly to semi-annually. Today, the fab has maintained a record of 21 years and counting with no unplanned shutdowns to clean heat exchangers. This reduction in cleaning frequency has yielded $42,850 in annual labor savings plus an additional $42,850 in annual chemical cleaning savings.

In addition, iron levels in the system water were reduced by 97%, from the previous high of as much as 30 ppm (indicating active corrosion) to 0.02-0.8 ppm. Enhanced corrosion protection supports the customer's ability to maximize uptime and meet the manufacturer's projected asset life for each PVAC unit.

While this story details the annual cost savings, it's important to note the enhanced value achieved by maintaining these gains: Through continued support and no unplanned cleanings in 21 years, the customer's cost savings have been compounded to reach $1.8 million in total.

eROI Logo
Annual Savings
Operational Performance
$85,700
Value Delivered
View definition
Total Value Delivered:
$85,700

Ecolab helped this customer improve:

  • Productivity
    • By reducing labor required for cleaning
    • By reducing cleaning chemical costs
  • Assets
    • By achieving a 97% reduction in iron levels in system water

Client-supplied data.

Related Success Stories

Partnering with customers to solve their greatest challenges.

qatest013

Success Story H2 Subtitle...

Korean automaker reduces wastewater sludge with expert support from Nalco Water

Korean automaker reduces wastewater sludge with expert support from Nalco Water...

3DTCOS Improves Low PH Events

3DTCOS Improves Low PH Events...

A Bold New Climate Commitment

Ecolab joins the Business Ambition for 1.5C, a group of global companies committed to doing their part to curb climate c...

HEAT Exchanger Reliability Management Success Story

Nalco Water Heat Optimized Maintenance Cost and Improved reliability for a Petrochemical Plant...

Ecolab Large Fly Program Reduces Large Flies in Quick Service Restaurants

In many quick service restaurants, flies congregate near the dumpster and may enter the restaurant through open doors or...

Reducing Rodent Risk Helps Protect Restaurant Brand

A national restaurant chain implemented Ecolab's Rodent Ceiling Service, resulting in more than 97% of locations having ...

Innovating for a Greener Paint Shop | Story

Through extensive research and rigorous field testing, we developed APEX™ Paint Detackification Technology, the first t...

Building an Action Plan for Smart Water Management

Digital Realty was on a mission to improve its water strategy, minimize overall water use, ensure reliable performance a...

Wringing Out Big Savings for Commercial Laundries

Five leading textile service groups in Australia and New Zealand recently turned to Ecolab to help them: reduce water an...

Dryexx Conveyor Lubricant, A Long Line of Savings

DryExx, a patented dry lubricant system, keeps bottling conveyor lines running smoothly while drastically cutting the am...

Pulp Wash Intelligence Delivers Consistently Clean Pulp

An integrated kraft mill producing 1,500 TPD in North America was looking to improve and automate its brown stock washin...